Contact
Start
Differential pressure switches PK50
Differential pressure switches PK50

Adjustable differential pressure switch for monitor ing
overpressure, vacuum and differential pressure of air or other
non-combustible, non-aggressive gases.
Maximum operating pressure
10 kPa for all pressure ranges.
Medium
Air, non-combustible and non-aggressive gases.
Temperature range
Medium and ambient temperature from –20°C to +85°C.
Storage temperature from –40°C to +85°C.
Diaphragm material
Silicone, tempered at 200°C, free of gas emissions.
Other materials available on request.
Pressure connections
2 plastic pipe connection pieces (P1 and P2), external
diameter 6.0 mm:
P1 for connection to higher pressure (marked +)
P2 for connection to lower pressure (marked –)
Housing materials
Switch body and cover of plastic.
Weight
With cover 150 g, without cover 110 g.
Mechanical working life
Over 106 switching operations.
Electrical rating
Standard version: max. 1.5 A (0.4 A) / 250 VAC
Low-voltage version: max. 0.1 A / 24 VDC
Electrical connections
AMP flat plug 6.3x0.8 mm in accordance with DIN 46244
or push-on screw terminals.
Cable conduit with cable strain relief.
Protection category
IP 54 with cover, IP 00 without cover.
Specifications according to EN1854
Class of control and regulation function: A
Deviation: ≤±15 %, min. ±10 Pa
Drift: ≤±15 %
Accessories
See order matrix.
Monitoring air filters and ventilators
Monitoring industrial cooling-air circuits
Overheating protection for fan heaters
Monitoring flows in ventilation ducts
Controlling air and fire-protection flaps
Frost protection for heat exchangers
Contact
Telephone: 302 300 1919
Fax: 302 300 1619
Mail: sales@ftisensors.com
1013 Centre Road, Suite 403S, Wilmington, DE 19805 USA